The IME TABB50C150 is a single-phase measuring current transformer (TAS102 series) with a ratio of 150/5 A.
The IME TABB50C150 is a single-phase measuring current transformer (TAS102 series) with a ratio of 150/5 A. It is designed for busbar or cable installations with a 38×102 mm window, offering accuracy class 0.5/1 and a rated burden of 20–25 VA.
Model: TABB50C150
Series: TAS102 (IME current transformers for busbars/cables)
Type: Measuring current transformer (single-phase)
Application: Converts medium primary currents into standardized secondary currents (5 A) for metering, analyzers, and protective relays.
Mounting: Busbar or cable installation with fixed window size (38×102 mm).
Electrical Specifications
Primary current (In): 150 A
Secondary current (Is): 5 A
Accuracy class: 0.5 / 1 (depending on metering or protection use)