Function: Allows direct connection of resistance sensors (e.g., Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000)
Certainly! Here are the key points about the Beckhoff KL3202 Bus Terminal:
Type: 2-channel analog input terminal
Function: Allows direct connection of resistance sensors (e.g., Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000)
Measurement Range: -200°C to +850°C (Pt sensors), -60°C to +250°C (Ni sensors)
Resolution: 0.1°C per digit
Connection Method: 2-wire or 3-wire (default: 3-wire)
Conversion Time: ~250 ms
Measurement Error: < ±1°C
Electrical Isolation: 500 V (K-bus/signal voltage)
Current Consumption: Typ. 60 mA (K-bus)
Special Features: Open-circuit recognition, sensor fault indication via error LEDs
Operating Temperature: -25°C to +60°C
Storage Temperature: -40°C to +85°C
Protection Rating: IP20